General Specifications |
|
Voltage AC (Un) |
230V |
Voltage Range |
176~276V AC |
Base Current (Ib) |
10A |
Max. Current (Imax) |
100A |
Mini Current (Imin) |
0.5A |
Starting current |
0.4% of Ib |
Power consumption |
<2W/10VA |
Frequency |
50/60Hz(±10%) |
AC voltage withstand |
4KV for 1 minute |
Impulse voltage withstand |
6KV-1.2uS wavform |
Overcurrent withstand |
30Imax for 0.01s |
Pulse output rate |
1000imp/kWh (Import) |
|
1000imp/kWh (Export) |
Display |
LCD with blue backlit |
Max. Reading |
99999.9kWh |
|
|
Accuracy |
|
Voltage |
0.5% of range maximum |
Current |
0.5% of nominal |
Frequency |
0.2% of mid-frequency |
Power factor |
1% of Unity |
Active power |
1% of range maximum |
Reactive power |
1% of range maximum |
Apparent power |
1% of range maximum |
Active energy |
Class 1 IEC62053-21 |
|
Class B EN50470-3 |
Reactive energy |
1% of range maximum |
|
|
Environment |
|
Operating temperature |
-25℃ to + 55℃ |
Storage and transportation temperature |
-40℃ to +70℃ |
Reference temperature |
23℃±2℃ |
Relative humidity |
0 to 95%, non-condensing |
Altitude |
up to 2500m |
Warm up time |
10s |
Mechanical Environment |
M1 |
Electromagnetic environment |
E2 |
Degree of pollution |
2 |
Output |
|
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse 1:Export active energy, constant 1000imp/KWh, pulse width 100ms, non-configurable
Pulse 2:Import active energy, constant 1000imp/KWh, pulse width 100ms, non-configurable
Mechanics
Din rail dimensions |
36x99x63 (WxHxD) DIN 43880 |
Mounting |
DIN rail 35mm |
Sealing |
IP51 (indoor) |
Material |
Self-extinguishing UL94V-0 |